HNL INSTRUMENTS & CONTROLS
800 series
specifications
Standard Electrical Smartstats:
Power Supply
24Vdc @ 3.5mA without 4 - 20mA transmission.
24Vdc @ 30mA with 4 - 20mA transmission.
Maximum supply voltage 30Vdc.
Switching
Relays have multi-layered contacts making them suitable for switching
from 100mVdc 100µA to 30Vdc 3A or 250Vac 4A.
Minimum switching life 100,000 operations.
I.S. Certified Smartstats:
EExia IIC T4/T5/T6 BS5501: Parts 1 & 7, EN50 014 & EN50 020.
T4 = 80°C, T5 = 55°C, T6 = 40°C. Certificate No. Ex94C2199.
Power Supply
24Vdc @ 3.5mA without 4 - 20mA transmission.
24Vdc @ 30mA with 4 - 20mA transmission.
24Vdc supply via any 28V 300ohm I.S. source certified by Baseefa or
any EEC approved certification body to EEx ia IIC.
For Smartstat supply C=0, L=0.
Suitable barriers include MTL702+, MTL3041, MTL5041 etc.
Switching
Each relay must be connected to a separate (or the same) I.S. source
certified by Baseefa or any EEC approved certification body to EEx ia
IIC whose output does not exceed 28Vdc.
Umax IN = 28Vdc, Imax IN=3.33A. For relay outputs C=0, L=0.
Suitable barriers include MTL707+, MTL2210B, MTL5016 etc.
All Smartstats:
Accuracy
Linearity Error: +/- 0.1% typical, +/-0.25% max.
Pressure hysteresis: +/- 0.1% max.
Temperature coefficient: 0.01% per °C typical, 0.025% max.
CE This product satisfies the
requirements of the Electromagnetic Compatibility Directive
89/336/EEC and amendments by compliance with standards EN50081-2:1993
and EN50082-2:1995. This product also complies with standard
EN60947-5-1:1991 in addition to the standards listed for hazardous
area certification. Refer to HNL datasheet S-306 for further
information.
BACK
HAMALL PROCESS INSTRUMENTS,
DEVONPARK MILLS, ALEXANDRA STREET, TILLICOULTRY, CLACKMANNANSHIRE,
SCOTLAND, UK. FK13 6HP
TEL NO : 44 (0)1259 753753 FAX NO : 44
(0)1259 752770
sales@hamall.co.uk
|