HNL INSTRUMENTS &
CONTROLS
Series 800 Smartstat

Range selection Coding Specifications
Download
temperature smartstat pdf datasheet(255K) Download
smartstat pdf datasheet(271K)
- Pushbutton calibration of set
points enables calibration on site without
tools.
- Programmable switching delays - the
switching on or off (or both) of the relays may be
delayed from 0.5 seconds to 15 minutes. This is
particularly useful for preventing unwanted switching due
to pressure transients.
- Display of Maximum and Minimum
pressures recorded by the Smartstat.
- Display of transmitter output in
mA.
- Displayed units of measurement -
can be changed by the user as required.
- Single point local annunciator
option - one relay is used for a local alarm and the
second for remote transmission of alarm. The second relay
can be configured for manual or auto
reset.
|
- 24vdc supply, 4-20ma loop
powered
- High accuracy and
repeatability
- Standard electrical and i.s.
Certified versions available
- Reduce costs
|
- Very high (or low)
pressures.
- High accuracy and
repeatability.
- Very large (or small) switching
differentials.
- Pressure ranges from -1 to 1000
bar
- Dp ranges from 15 mbar to 4
bar
|
The Series 800 Smartstat is a microprocessor controlled
pressure switch, transmitter and indicator, which enables several
instruments to be replaced with a single device.
There are some pressure and differential pressure (DP) switching
applications that are very demanding due to the need for :-Very high
(or low) pressures, high accuracy and repeatability, very large (or
small) switching differentials. These requirements may exceed the
capabilities of conventional mechanical pressure switches, the
Smartstat was designed to overcome these problems.
The Smartstat is available with pressure ranges from 100 mBar to 1000
Bar, and DP ranges from 15 mBar to 4 Bar providing a typical accuracy
of 0.1%.
Two independent single-pole, double-throw (SPDT) relays are fitted in
the Smartstat, the operating points of which can be set anywhere
within the range. The switching differential can be set from 0.1% to
100.0% of range without loss of accuracy.
SUBSTANTIAL COST SAVINGS
Replacing a transmitter, switches and a gauge with a single Smartstat
reduces equipment costs. Additionally there are reductions in
documentation, installation time/ fittings/cabling, and
calibration/maintenance costs.