HNL INSTRUMENTS & CONTROLS
Series 300 Range
Codes
The tables below detail the Series 300
Pressure and Differential Pressure (DP) ranges available.
For each Range Code the range of adjustment of the switching point is
given from MIN to MAX together with the units of measurement. E.g.
The set point adjustment for a 344P is from 0.1 to 1.4 bar.
The % RESET figure (or switching differential) is the difference in
pressure that must be applied to change the output switch state from
ON to OFF (or OFF to ON), and is expressed as a percentage of the
switch range.
There are three standard diaphragm material options 1 - nitrile, 2 -
PTFE and 7 - hastelloy C. Availability of a given diaphragm material
for a selected range is indicated by a *, a blank indicates the
diaphragm material is not available.
There are three standard process chamber material options 1 -
aluminium, 5 - 316 stainless steel and 7 - hastelloy C. Availability
of a given chamber material is indicated by a number in the
appropriate column for a selected range. This number is the chamber
proof pressure rating in bar. A blank would indicate that the chamber
material is not available, a # indicates that availability must be
checked.
| PRESSURE RANGES (PRESSURES ARE
GAUGE) |
Setpoint ranges (DP
and DPZ)
|
Diaphragm material |
Chamber proof rating (bar)
|
Min
|
Max |
Units |
Range code |
% reset |
Aluminium |
Stainless
steel |
Hastelloy
C |
| 1 2 7 |
1 |
5
|
7 |
-8
-15 |
8
15 |
mBar
mBar |
314PZ
315PZ |
2 |
* *
* * |
|
0.5
0.5 |
|
-25
-50 |
25
50 |
mBar
mBar |
324PZ
325PZ |
2 |
* * *
* * * |
2
2 |
2
2 |
#
# |
-125
-250
-500 |
125
250
500 |
mBar
mBar
mBar |
334PZ
335PZ
336PZ |
2 |
* * *
* * *
* * * |
10
10
10 |
10
10
10 |
#
#
# |
-0.6
-1
-1 |
0.6
1.4
6 |
Bar
Bar
Bar |
344PZ
345PZ
346PZ |
2 |
* * *
* * *
* * * |
30
30
30 |
30
30
30 |
#
#
# |
25
50
100
300 |
250
500
1200
3500 |
nBar
mBar
mBar
mBar |
334P
335P
336P
337P |
2 |
* * *
* * *
* * *
* * * |
10
10
10
10 |
10
10
10
10 |
#
#
#
# |
0.1
0.2
0.7
2 |
1.4
3
7
21 |
Bar
Bar
Bar
Bar |
344P
345P
346P
347P |
2 |
* * *
* * *
* * *
* * * |
30
30
30
35 |
30
30
30
35 |
30
30
30
35 |
1.2
3
7
20
60 |
12
30
70
210
600 |
Bar
Bar
Bar
Bar
Bar |
354P
355P
356P
357P
358P |
3 |
* *
* *
* *
* *
*
|
|
250
250
250
350
1000 |
250
250
250
350
1000 |
| DIFFERENTIAL PRESSURE RANGES (PRESSURES ARE
DP) |
Setpoint ranges (DP
and DPZ)
|
Diaphragm material |
Chamber proof rating
(bar)
|
| Min |
Max |
Units |
Range code |
% Reset |
Aluminium |
Stainless steel |
Hastelloy C |
| 1
2 7 |
1 |
5 |
7 |
|
-8
-15
|
8
15
|
mBar
mBar
|
314DPZ
315DPZ |
2.5 |
* *
* * |
|
0.5
0.5 |
|
|
-25
-50
|
25
50
|
mBar
mBar
|
324DPZ
325DPZ |
2.5 |
* * *
* * * |
2
2 |
2
2 |
#
# |
|
-125
-250
|
125
250
|
mBar
mBar
|
334DPZ
335DPZ |
2.5 |
* * *
* * * |
10
10 |
10
10 |
|
|
-100
-200
-400
|
100
200
400
|
mBar
mBar
mBar
|
334DPZM
335DPZM
336DPZM |
3 |
*
*
* |
|
300
300
300 |
|
|
25
50
100
300
|
250
500
1200
3500
|
mBar
mBar
mBar
mBar
|
334DP
335DP
336DP
337DP |
2.5 |
* * *
* * *
* * *
* * * |
10
10
10
10 |
10
10
10
10 |
#
#
#
# |
|
20
40
100
300
|
200
400
1000
3000
|
mBar
mBar
mBar
mBar
|
334DPM
335DPM
336DPM
337DPM |
3 |
*
*
*
* |
|
300
300
300
300 |
|
|
0.7
2
10
|
7
21
100
|
Bar
Bar
Bar
|
346DPM
347DPM
348DPM |
3 |
*
*
* |
|
300
300
300 |
|
BACK
HAMALL PROCESS INSTRUMENTS,
DEVONPARK MILLS, ALEXANDRA STREET, TILLICOULTRY, CLACKMANNANSHIRE,
SCOTLAND, UK. FK13 6HP
TEL NO : 44 (0)1259 753753 FAX NO : 44
(0)1259 752770
sales@hamall.co.uk
|